Johnson Controls HVAHP036B21S - Dry Operation

Johnson Controls HVAHP036B21S
94 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OUTDOOR UNITS
TC-16001-rev.5
2-17
n
Dry Operation
Press
AUTO-LOUVER
Switch
< Alternately >
Start of
Auto-Louver
Stop of
Auto-Louver
only for Decorative Panel
or Indoor Unit
with Auto-Louver
Power to
I.U.: ON
Power to
O.U. PCB: ON
Power to
I.U. PCB: ON
Power to YH2
in I.U.: OFF
only for indoor unit
with auto-louver
Auto-Louver
0 Reset
“DRY” Indication
RUN Indicator: ON
Start of Communication between
I.U. and O.U.
Start of Communication between
I.U. and Wired Controller
Power to YH2 : ON
ON
(Lower than
Activation Level)
OFF
(Higher than
Activation Level)
Power to YH2
in I.U.: ON
Press
RUN/STOP
Switch
Power to
O.U.: ON
Set
Operation Mode
to “DRY”
for unit with drain pump
To 2
Dry Operation
No
Yes
Yes
No
Power to MC : OFF
Power to MIF : OFF
FS
Power to CH : ON
Power to CH : OFF
Temp. at To p
of Compressor
> 23
o
F
(-5
o
C)
< 23
o
F (-5
o
C)
No
Yes
I.U. Air
Inlet
Temp.
Outdoor
Temp.
Press
TEMP. Setting
Switch
Indication of Set Temp.
Switch: To increase Set Temp.
Switch: To decrease Set Temp.
Power to
Y52C :
ON
MOF Operation
: ON
Power to MC :ON
> Set Temp.
< Set Temp.
Elapsed Time:
1sec.
Elapsed Time:
6 min.
Elapsed Time:
6 min.
I.U. : Indoor Unit
O.U. : Outdoor Unit
: Actuator (refer to Table 2.1)
MIF Operation at Low Fan Speed
MD Operation: ON
MIF Operation at Low Fan Speed
< 86
o
F (30
o
C)
or
< Outdoor Temperature +45
o
F (+25
o
C)
> 86
o
F (30
o
C)
and
> Outdoor Temperature +45
o
F (+25
o
C)