OUTDOOR UNITS
TC-16001-rev.5
2-11
2.9 Electrical Data
Model
Outdoor Unit INV Comp.
Hz Voltage Max. Min. MCA MOP Max. Fuse RLA LRA
[Hz] [V] [V] [V] [A] [A] [A] [A] [A]
(H,Y,C)VAHP036B21S 60 208/230 228/253 188/207 31 40 40 24 30
(H,Y,C)VAHP048B21S 60 208/230 228/253 188/207 31 40 40 24 30
(H,Y,C)VAHP060B21S 60 208/230 228/253 188/207 31 40 40 24 30
Model
Fan Motor Wiring Size Conduit Tube
Output FLA
Power Supply
Wiring
Ground Wiring
Communication
Cable
for Power
Supply Wiring
[kW] [A] [AWG] [AWG] [AWG] [in. (mm)]
(H,Y,C)VAHP036B21S 0.058+0.058 0.5+0.5 8 8 18 3/4 (19.05)
(H,Y,C)VAHP048B21S 0.058+0.058 0.5+0.5 8 8 18 3/4 (19.05)
(H,Y,C)VAHP060B21S 0.058+0.058 0.5+0.5 8 8 18 3/4 (19.05)
MCA: Minimum Circuit Ampacity (A)
MOP: Maximum Overcurrent Protective Device (A)
RLA: Rated Load Ampacity (A)
LRA: Locked Rotor Ampacity (A)
FLA: Full Load Ampacity (A)