JOHNSON CONTROLS
18
FORM 145.05-FA1
ISSUE DATE: 10/31/2019
SECTION 2 - MEDIUM CABINET FIELD REASSEMBLY
Gasket
Material
LD14983
FIGURE 31 - FILTER RACK
26. Verify the gasket material is intact and not dam-
aged on the lter section. If damaged, repair the
gasket prior to joining the coil section to the lter
section (Figure 31 on page 18).
27. There is an angle on the top of the lter rack that
ts into a slot in the top of the coil section. Lift the
lter rack up and then down so that it hangs from
the slot in the top of the coil section. Figure 32 on
page 18 shows a detail of how the lter rack ts
into the slot at the top of the coil section.
Hanger
Angle
COIL
SECTION
FAN
SECTION
Slot
LD15024
FIGURE 32 - FILTER RACK ATTACHMENT
28. From Table 4 on page 14, use ten 10 - 16 x 3/4-
inch screws, ve on each side of the lter rack,
to fasten it to the coil section. Use the clearance
holes in the lter rack side mounting rails as a
template to identify the proper location for the in-
stallation of the screws.
29. Refer to the unit Installation, Operation, and Main-
tenance (IOM) manual (Form 145.05-NOM7) and
Quick Start-Up Guide (Form 145.05-SU7) to con-
tinue the installation and start-up.