JOHNSON CONTROLS
8
FORM 145.05-FA1
ISSUE DATE: 10/31/2019
SECTION 1 - SMALL CABINET FIELD ASSEMBLY
TABLE 2 - SMALL CABINET FILTER SECTION
PARTS LIST
ITEM PART NUMBER DESCRIPTION QTY
1 021-30530-001 Screw, 10 - 16 x 3/4-inch 10
REASSEMBLY PROCEDURE
Do not connect the main unit power at
this time.
1. Position the unit sections in their approximate -
nal location.
2. Remove the packaging material from the unit
sections.
3. Examine the unit sections for damage and report
any damage to the carrier.
4. Verify the gasket material around the supply fan
opening on the coil section is intact and not dam-
aged (Figure 2). If damaged, the gasket must be
repaired prior to joining the two units.
5. Prior to pushing the two sections together, remove
the compressor access panels, water valve access
panel (Figure 3), and the coil access panel (Figure
4) from the coil section of the unit. This allows
access to install the bolts in Steps 20. Retain the
panels and hardware for installation in Step 21.
Gasket
Material
LD15018
FIGURE 2 - VIEW OF GASKET MATERIAL APPLIED
AROUND SUPPLY FAN OPENING
6. Prior to pushing the two sections together, place
the wiring through the cutout and into the coil sec-
tion (Figure 5 on page 9).
Coil
Door
Compressor
Water
Valve
Access
Panel
LD15019
FIGURE 3 - COIL SECTION, ISOMETRIC VIEW
Coil Access
Panel
LD15015
FIGURE 4 - COIL SECTION, SIDE VIEW
7. Push the two sections together so that the rectan-
gular opening in the coil section aligns with the
rectangular hole containing the mating plug con-
nections in the fan section (Figure 6 on page 9).