RW SERIES REVERSIBLE CHILLER INSTALLATION MANUAL
Menu and Menu Contents
Alarm
Displays unit alarms until the unit has been reset (Unit alarms
can be reset by holding both the Escape (ESC) key and Return
() key for five seconds or by power cycling the unit.)
Alarm History
If a fault occurs the fault will be recorded in history viewable on the
unit mounted display. Each fault type will be displayed in the history
menu with a number between 0 and 3. A reading of 3+ means that
the fault has occurred more than 3 times in the past. The history
menu can be cleared with a power cycle only. Alarm date and time
are not included in the history.
Unit Alarms
Unit alarms are shown on the display once the unit has locked out.
Load Flow – Load Flow Switch is Not Closed
The load flow switch must be closed prior to either
compressor starting and must remain closed for the entire run
time of the compressor(s).
Low Pressure 1 – Compressor Circuit 1 Low
Pressure Switch
The low pressure switch is checked before compressor start up
and is monitored during compressor operation.
Src FP 1 Temp Low – Source Freeze
Detection Sensor 1
The source freeze detection sensor on compressor circuit 1 has
reached its setpoint.
Src FP 1 Sensor Bad
The sensor for source freeze detection on compressor circuit 1
is unreliable or is not reading.
LD FP 1 Temp Low – Load Freeze Detection Sensor 1
The load freeze detection sensor on compressor circuit 1 has
reached its setpoint.
LD FP 1 Sensor Bad
The sensor for load freeze detection on compressor circuit 1 is
unreliable or is not reading.
Source Flow – Source Flow Switch is Not Closed
The source flow switch must be closed prior to either
compressor starting and must remain closed for the entire run-
time of the compressor(s).
Unit Display and Interface cont.
High Pressure 1 – Compressor Circuit 1 High
Pressure Switch
If high pressure switch 1 opens at any time during compressor 1 run
time the compressor will be shut down immediately.
Low Pressure 2 - Compressor Circuit 2 Low
Pressure Switch
The low pressure switch is checked before compressor start up
and is monitored during compressor operation.
Src FP 2 Temp Low - Source Freeze Detection Sensor 2
The source freeze detection sensor on compressor circuit 2 has
reached its setpoint.
Src FP 2 Sensor Bad
The sensor for source freeze detection on compressor circuit 2
is unreliable or is not reading.
LD FP 2 Temp Low - Load Freeze Detection Sensor 2
The load freeze detection sensor on compressor circuit 2 has
reached its setpoint.
LD FP 2 Sensor Bad
The sensor for load freeze detection on compressor circuit 2 is
unreliable or is not reading.
High Pressure 2 - Compressor Circuit 2 High
Pressure Switch
If high pressure switch 2 opens at any time during compressor 2 run
time the compressor will be shut down immediately.
Comp Start Failure – Compressor Start Failure
If either compressor fails to start when the contactor pulls in the
compressor current switch will cause that compressor to be locked
out after 2 retries. The other compressor will continue to operate
normally in this condition.