29
RW SERIES REVERSIBLE CHILLER INSTALLATION MANUAL
Operating Parameters
NOTE: Operating data based on normal conditions with 4 gpm/ton for the load and source.
NOTE: Operating data based on normal conditions with 4 gpm/ton for the load and source.
Heating Mode
Entering
Load Temp (
o
F)
Entering
Source Temp (
o
F)
Suction
Pressure (psig)
Discharge
Pressure (psig)
Superheat
(
o
F)
Subcooling
(
o
F)
60
30 75-100 200-215 10-12 10-13
50 100-125 200-215 12-14 8-12
70 125-150 215-230 14-18 8-12
90 150-165 230-255 25-30 8-12
80
30 75-100 285-300 10-12 10-13
50 100-125 300-315 12-14 8-12
70 125-150 315-330 14-18 8-12
90 150-165 330-345 25-30 8-12
100
30 85-110 365-380 10-12 7-11
50 110-135 385-400 12-14 7-11
70 135-165 400-415 14-18 3-7
120
50 110-135 485-500 12-14 7-11
70 135-165 500-515 14-18 3-7
1/30/14
Cooling Mode
Entering
Load Temp (
o
F)
Entering
Source Temp (
o
F)
Suction
Pressure (psig)
Discharge
Pressure (psig)
Superheat
(
o
F)
Subcooling
(
o
F)
50
30 80-90 140-175 15-20 3-6
50 90-100 200-235 11-15 6-9
70 100-110 250-285 11-15 9-12
90 100-120 330-365 8-12 12-14
110 110-130 430-465 8-12 14-19
70
30 80-90 150-185 15-20 3-6
50 90-100 210-245 11-15 6-9
70 100-110 260-295 11-15 9-12
90 110-120 340-375 8-12 12-14
110 110-140 440-485 8-12 14-19
90
30 80-90 150-185 15-20 3-6
50 90-100 210-245 11-15 6-9
70 100-110 260-295 11-15 9-12
90 110-120 340-375 8-12 12-14
110
30 90-100 160-195 40-45 3-6
50 110-130 220-255 30-40 6-9
1/30/14