Safety precautions
4.8 Sound and noise data
4.8.1 Noise data
Noise data is stated in:
SWL:
A-weighted sound power level
SPL:
A-weighted sound pressure level, in free field over reflecting plane (1 m distance).
Noise data is based on measurements according to ISO 9614-2.
The stated SPL values are calculated using the formula 8.3 in ISO 3744.
The stated values are for a complete unit operating in 100% capacity.
4.8.2 Noise data for SAB 355
Evaporating temperature, TE -15°C
Condensing temperature, TC
+35°C
Refrigerant R717/HCFC/HFC
Speed
2950 rpm
For 60 Hz-driven compressors, add +2 dBA to the stated levels.
Type of unit
SWL SPL
SAB 355 S 112 89
SAB 355 L 112 89
SAB 355 E 112 89
SAB 355 X 112 89
Table 5: Noise data
Noise data for other operating conditions can be provided by Johnson Controls Denmark on
request.
Note:
The actual SPL value on site will be between the stated SPL and SWL depending on the
acoustic environment in the machine room.
In a typical machine room without any noise absorbing materials, the actual SPL will be
approximately 14 dBA higher than the stated SPL (free field value).
Checking the actual SPL must therefore always be accompanied by measurements of the
acoustic environment of the machine room. Alternatively, ISO 9614-2 could be followed
at the installation site to obtain SWL comparable values.
Be aware of local/national requirements for the use of ear protection. Generally, it is rec-
ommended to use ear protection in machine rooms.