Version no. Description
1.0.5.0 A number of new chiller control and supervision functions for oil return, by-
pass, flow switch and level control have been added.
Display and supervision of Process in temp. for chiller has been added.
For SABCube compressor types SAB 109-159 the start-up limiter function has
been changed.
The SABCube VSD menu for the LS drive has been updated with menu lists.
A new oil filter differential pressure function for the SMC 1xx/TSMC/HPC type
reciprocating compressors has been added.
Brazilian language has been added.
A problem with OPC/RS2LAN in slave mode where the communication was not
stable and therefore issued node alarms has been corrected.
A problem with Comsab II in master mode where Comsab II had problems
taking over the master role from a running Unisab III master has been correc-
ted.
For SAB 120-151 the calculated capacity start and stop limit are increased
from 5% to 10%.
An oil pump error on VMY Mk2 where the oil pump did not start if the com-
pressor stopped at a capacity > 5% has been corrected.
The emergency stop is now connected to DI4 which makes it possible to dis-
tinguish between a compressor motor error and whether the emergency stop
has been pressed.
The password inactivity timer has been increased from 2 to 15 minutes for
User and Superuser level. For Supervisor level it is still approximately 1 mi-
nute.
The SABHMI application can now be started with the IP number as parameter.
Using the string: /REM:xxx.xxx.xxx.xxx connects SABHMI remotely on win-
dows start-up.