Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
275/346
UniSAB III (boot) and communication set-up
Press Yes to proceed.
When the transfer is completed, press OK and UniSAB III will display “Has config files”.
Now you can remove the SD card from UniSAB III, insert it in your PC, copy the files to a drive position
or import the files directly into e.g. U Set. This transfer operation provides you with all 10 .xml files plus a
vfd.dat and a watchdogLog.log file. Only four of these files are accessible by U Set as described in 8.8 U
Set configuration tool.
The following files can be downloaded and edited by U Set:
Configuration.xml - this file contains the UniSAB III configuration and calibration values
AnalogInput.xml - this file contains shutdown/alarm limits and set points
PIDSettings.xml - this file contains PID regulator parameters, like Ti, Td and Ts
Timers.xml - this file contains the UniSAB III timers setting
The following .xml files will be downloaded too:
UniqueConfig.xml - (configuration file, version info, IP setup)
HMIsettings.xml - (configuration file, favourite’s setup)
R000Table.xml - (configuration file, refrigerant R000 setup)
Modbus.xml - (Modbus TCP address look up file)