NOTE
Not all configurations can detect all states. For more information regarding states, refer to the I/8-CSI User Guide and the con-
figuration tables and images relevant to the configuration of your unit.
IP-ACM Ethernet Door Module v2 power and wiring requirements
Table 4 on Page 5 describes the power and wiring requirements for the IP-ACM v2.
Table 4:Power and wiring requirements for the IP-ACM v2
Signal Power Requirements To AWG Shield Maximum Length
RS-485 Comm,
Data half duplex 2-
wire
RM & I/O modules 22 Yes 4000ft (1212m)
NOTE: If using tthe TST-100
Touchscreen Terminal
reader, then the
maximum distance is
32ft (10m).
RS-485 Power
12Vdc
1
RM & I/O modules 22/18 Yes Maximum length depends on
application and AWG
2
RJ45-Ethernet Level 3 Switch, Hub, or
Host
CAT-5E
or better
No 328ft. (100m)
Request to Exit
(REX or RTE)
Switch Contact 22/18 No 2000ft. (606m)
Door State
Monitor (DSM)
Switch Contact
Supervised Input
(UL) Note
3
Input 22 Yes 2000ft. (606m)
Reader Data
(Direct Wiegand
Connection)
12Vdc
4
Proximity/Wiegand
signaling read head
22
20
18
Yes 200ft. (60.96m)
300ft. (91.4m)
500ft. (152.4m)
Wet Relay
Contacts
12 or 24Vdc (jumper
selectable), 0.5A (per lock)
5
2000ft. (606m)
Dry Relay
Contacts
0 to 30Vdc , 5A max. NO,
3A max. NC
2000ft. (606m)
1
It is important to note that the aggregate load of each pair of RS-485 and Wiegand connections together must not exceed 750mA. Each set of RS-485
and Wiegand can support 750mA.
2
Check wire lengths to verify that voltage drops are acceptable. Calculations are based on a single RM-4 reader with keypad and LCD (250mA). Using
22AWG, distance = 600ft. (.0165 ohms/ft.). Using 18AWG, distance = 1500ft. (.0065 ohms/ft.).
3
To comply with UL requirements, use shielded, minimum 22 AWG stranded, twisted pair cable for monitor points, DSMs, and REXs. Use Belden 9462 or
equivalent.
4
It is important to note that the aggregate load of each pair of RS-485 and Wiegand connections together must not exceed 750mA. Each set of RS-485
and Wiegand can support 750mA. Maximum combined output limit for readers, locks, and board logic is 20W.
5
Voltage depends on selection of power feed (L1 or L2). Maximum combined output limit for readers, locks, and board logic is 20W.
5