Power Requirements
iSTAR Ultra Installation and Configuration Guide 2–7
Power Requirements
Electrical
This section provides the power requirements for the iSTAR Ultra and its components.
Electrical ratings are dependent upon the configuration.
GCM
Power Input (12 Vdc ± 20%)
12 Vdc , 1.5A minimum, 4.5A maximum (if fully loaded)
Power Output
RS485: 12 Vdc , (11.14 Vdc as measured), 1.5A maximum per port
ACM
Power Input (12 Vdc ± 20%)
• Vreader: 12 Vdc , 12.5A maximum.
• Vlock1: 0 - 30 Vdc , 12A maximum.
• Vlock2: 0 - 30 Vdc , 12A maximum.
Power Output
• RS485 AUX: 12 Vdc , (11.64 Vdc as measured), 1.5A maximum each
• Wiegand/AUX: 12 Vdc , 800MA maximum each
• Primary Wet Relay Out: 0 - 30 Vdc , 0.75A maximum each
• Secondary Wet Relay Out: 0 - 30 Vdc , 0.75A maximum each
• Secondary Dry Relay Out: 0 - 30 Vdc , 1A maximum each
IP-ACM
Power Input
• 12 or 24 Vdc 32W maximum
• IEEE 802.3af (PoE) and 802at (PoE Plus), 25.5W max. LLDP supported for PoE Plus
Power Output
• RS485/Wiegand: 12 Vdc; The aggregate load of each pair of RS-485 and Wiegand
connections together must not exceed 750mA. Each set of RS-485 and Wiegand can
support 750mA. Maximum combined output limit for readers and locks is 20W.
• Wet Relay: 12 or 24 Vdc (jumper selectable), 0.5A (per lock)
• Dry Relay: 0 to 30 Vdc, 5A max. NO, 3A max. NC
NOTE
The Wiegand, RS-485, and Aux ports are power limited on the ACM.