LEL TEMP SET
LEL TEMP CE
LOW LELT
HIGH LCLT
LEP UNLOAD
LEP SHUT DOWN
HOLD LOAD D.P
UNLOAD D.P
HIGH D.P.SHUTDOWN
UNLOAD CURR.
DELTA T
Defult values
7.0
1.0
2.0
43.0
175KPa
165KPa
1030KPa
1060KPa
1090KPa
95%
3.5
Setting range
4.0~15.0
0.5~2.0
1.0~7.0
30.0~60.0
150.0~300.0 KPa
150.0~300.0 KPa
100.0~1300.0 KPa
100.0~1300.0 KPa
100.0~1350.0 KPa
10~98%
2.0~6.0
Access level
User password
User password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
(2) Assignable parameters setting and defult values (AC mode)
(3) Assignable parameters setting and defult values (ITS mode)
Items
LEL TEMP SET
LEL TEMP CE
LOW LELT
CR BUFFER
HIGH LCLT
LEP UNLOAD
LEP SHUT DOWN
HOLD LOAD D.P
UNLOAD D.P
HIGH D.P.SHUTDOWN
UNLOAD CURR.
DELTA T
LISV TEMP
Setting range
-8.0~+5.0
0.5~2.0
-15.0~+5.0
1.0 2.5
30.0~60.0
80.0~300.0 KPa
80.0~300.0 KPa
100.0~1300.0 KPa
100.0~1300.0 KPa
100.0~1350.0 KPa
10~98%
2.0~6.0
50.0~80.0
Defult values
-5.6
1.0
2.0
2.5
43.0
175KPa
165KPa
1030KPa
1060KPa
1090KPa
95%
4.5
70.0
Access level
User password
User password
Service password
User password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
YEWS-E Water Cooling Screw Chiller/Heat Pump
41