YORK, A Johnson Controls Company %**8=9);
1. More than 3 relays requires the addition of a relay extension module.
2. Applies only for Modbus using YORK Drive profile.
3. BACnet not defined at time of publication.
\2/@_ To control relays 1 and 2 using serial communication:
Set parameters 1401
RELAY OUTPUT 1 and 1402 RELAY OUTPUT 1 = 35 (COMM).
Then, for example using N2:
• To turn Relay 1 On: Force object B07 to On.
• To turn Relay 2 On: Force object B08 to On.
• To turn both Relay 1 and 2 On: Force objects B07 and B08 On.
2,8 Relay status feedback occurs without configuration as defined below.
1. Applies only for Modbus using YORK Drive profile.
2. BACnet not defined at time of publication.
27&,,2,2
Using the fieldbus for analog output control (e.g. PID setpoint) requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied analog value(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
1. Applies only for Modbus using YORK Drive profile.
2. BACnet not defined at time of publication.
%*2,2#,2,#2=
Using the fieldbus for the PID control setpoint requires:
• Drive parameter values set as defined below.
%@, #,,7
%2,2=2!4=
23;
F \" J,
F
0122 RO 1-3 STATUS Relay 1…3 status. 40122 BI4…BI6 76…78
0123 RO 4-6 STATUS Relay 4…6 status. 40123 BI7…BI9 79…81
%@, #,,7
%2,2=2!4=
23;
F \" J,
F
1501 AO1 CONTENT SEL 135 (COMM
VALUE
1)
Analog Output 1
controlled by
writing to
parameter 0135.
––––
0135
COMM VALUE 1 – 40135 AO14 46
1507
AO2 CONTENT SEL 136 (COMM
VALUE
2)
Analog Output 2
controlled by
writing to
parameter 0136.
––––
0136
COMM VALUE 2 – 40136 AO15 47