EasyManua.ls Logo

Johnson Controls York AYK550 - Application Macros; Macro Overview and Selection

Johnson Controls York AYK550
279 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
 
$ YORK, A Johnson Controls Company
=,2=2
&?
Macros change a group of parameters to new, predefined values designed for
specific applications. Use macros to minimize the need for manual editing of
parameters. Selecting a macro sets all other parameters to their default values,
except:
Group 99: Start-up Data parameters
The
PARAMETER LOCK 1602
The
PARAM SAVE 1607
Groups 50…52 serial communication parameters
Group 29: Maintenance triggers
After selecting a macro, additional parameter changes can be made manually using
the control panel.
Application macros are enabled by setting the value for parameter 9902
APPLIC
MACRO
. By default, HVAC default (value 1) is the enabled macro.
23,2
The following considerations apply for all macros:
When using a direct speed reference in AUTO mode, connect the speed
reference to analog input 1 (AI1), and provide the START command using digital
input 1 (DI1). In HAND/OFF mode, the control panel provides the speed
reference and START command.
When using process PID, connect the feedback signal to analog input 2 (AI2). As
a default, the control panel sets the Setpoint, but analog input 1 can be used as
an alternate source. You can set up process PID using parameters (Group 40) or
using the PID control assistant (recommended).
=,2`=2",7
This section describes the following macros:
kkF

=2
kkF

=2
1 HVAC default
8 Internal timer
2 Supply fan
9 Internal timer with constant speeds
3 Return fan
10 Floating point
4 Cooling tower fan
11 Dual setpoint PID
5 Condenser 12 Dual setpoint PID with constant speeds
6 Booster pump 13 E-bypass
7 Pump alternation
14 Hand Control

Related product manuals