EasyManua.ls Logo

Johnson Controls York AYK550 - Parameter Descriptions; Start-Up and Operating Data Parameters

Johnson Controls York AYK550
279 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 
$ YORK, A Johnson Controls Company
%@,=,2
Parameter data is specific to AYK550 firmware version 1.51.
2kk_#,,,
This group defines special Start-up data required to:
Set up the drive.
Enter motor information
2,8 Parameters checked under the heading “S” can be modified only when the
drive is stopped.
2kk_#,,,
23 =,2 !7 !2,2 4, #
9901 " 
Selects the display language.
9902 %%"*!& ] 9
Selects an application macro. Application macros automatically edit parameters to configure the AYK550 for a
particular application. See "Application Macros" for application macro descriptions.
1 =
HVAC DEFAULT
2 =
SUPPLY FAN
3 =
RETURN FAN
4 =
COOLING TOWER FAN
5 =
CONDENSER
6 =
BOOSTER PUMP
7 =
PUMP ALTERNATION
8 =
INTERNAL TIMER
9 =
INTERNAL TIMER WITH CONSTANT SPEEDS
10 =
FLOATING POINT
11 =
DUAL SETPOINT PID
12 =
DUAL SETPOINT PID WITH CONSTANT SPEEDS
13 =
E -BYPASS (Not used by YORK)
14 =
HAND CONTROL
9904 &'&!'!"& BQ Q 9
Selects the motor control mode.
1 = VECTOR: sPEED – sensorless vector control mode. (Not used in YORK HVAC applications)
Reference 1 is speed reference in rpm.
Reference 2 is speed reference in % (100% is absolute maximum speed, equal to the value of parameter 2002
MAXIMUM SPEED, or 2001 MINIMUM SPEED if the absolute value of the minimum speed is greater than the maximum
speed).
3 =
SCALAR: FREQ – scalar control mode. (Used for HVAC)
Reference 1 is frequency reference in Hz.
Reference 2 is frequency reference in % (100% is absolute maximum frequency, equal to the value of parameter
2008
MAXIMUM FREQUENCY, or 2007 MINIMUM FREQUENCY if the absolute value of the minimum speed is greater
than the maximum speed).
0 = ENGLISH 1 = ENGLISH (AM)2 = DEUTSCH 3 = ITALIANO
4 = ESPAÑOL 5 = PORTUGUES 6 = NEDERLANDS 7 = FRANCAIS
8 = DANSK 9 = SUOMI 10 = SVENSKA

Related product manuals