EasyManua.ls Logo

Johnson Controls York AYK550 - Timer and Constant Speed Functions

Johnson Controls York AYK550
279 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
, 
$ YORK, A Johnson Controls Company
2F_2,,#3
This group defines a set of constant speeds. In general:
You can program up to 7 constant speeds, ranging from 0…500 Hz or 0…30000
rpm.
Values must be positive (No negative speed values for constant speeds).
Constant speed selections are ignored if:
the torque control is active, or
the process PID reference is followed, or
the drive is in local control mode, or
PFA (Pump and Fan Alternation) is active
2,8 Parameter 1208 CONST SPEED 7 acts also as a so-called fault speed which
may be activated if the control signal is lost. Refer to parameter 3001
AI<MI FUNCTION
and parameter 3002 PANEL COMM ERROR. For HVAC, do not set speeds over 60 Hz.
2F_2,,#3
23 =,2 !7 !2,2 4, #
1201 &#'#%#" ]k 3 9
Defines the digital inputs used to select Constant Speeds. See general comments in the introduction.
0 =
NOT SEL – Disables the constant speed function.
1 =
DI1 – Selects Constant Speed 1 with digital input DI1.
Digital input activated = Constant Speed 1 activated.
2…6 =
DI2…DI6 – Selects Constant Speed 1 with digital input DI2…DI6. See above.
7 =
DI1,2 – Selects one of three Constant Speeds (1…3) using DI1 and DI2.
Uses two digital inputs, as defined below (0 =
DI de-activated, 1 = DI activated):
Can be set up as a so-called fault speed, which is activated if the control signal is lost. Refer to parameter 3001
AI<MIN function and parameter 3002 PANEL COMM ERR.
8 = DI2,3 – Selects one of three Constant Speeds (1…3) using DI2 and DI3.
See above (
DI1,2) for code.
9 =
DI3,4 – Selects one of three Constant Speeds (1…3) using DI3 and DI4.
See above (
DI1,2) for code.
10 =
DI4,5 – Selects one of three Constant Speeds (1…3) using DI4 and DI5.
See above (
DI1,2) for code.
11 =
DI5,6 – Selects one of three Constant Speeds (1…3) using DI5 and DI6.
See above (
DI1,2) for code.
* *F \=,2
0 0 No constant speed
1 0 Constant speed 1 (1202)
0 1 Constant speed 2 (1203)
1 1 Constant speed 3 (1204)

Related product manuals