EVAPORATOR SCREEN
JOHNSON CONTROLS
25
FORM 160.72-O1 (810)
Leaving Chilled Liquid Temperature Cycling
Offset - Restart
Access Level Required: OPERATOR
This value allows the user to specify the Leaving Chilled
Liquid Temperature at which the chiller will restart af-
ter a shutdown on a LEAVING CHILLED LIQUID
-LOW TEMPERATURE cycling shutdown. This is
done by defining an offset above the Leaving Chilled
Liquid Temperature setpoint. It is programmable over a
range of 0°F to 70°F above the setpoint, to a maximum
restart value of 80°F. The chiller will automatically re-
start when this temperature is reached. This setpoint
can be used to reduce chiller cycling by delaying the
chiller restart until the cooling load has increased.
PROGRAMMABLE
Refrigerant (Enabled / Disabled)
Access Level Required: SERVICE
When an Evaporator Refrigerant Temperature Sensor
has been installed it must be enabled via this toggle
before the system will utilize the new, enhanced reso-
lution input. Service Technicians refer to the Service
Instructions (Form 160.72-M1).
NAVIGATION
Home
Access Level Required: VIEW
Returns user to Home Screen.