FORM 160.72-O1 (810)
JOHNSON CONTROLS
40
MOTOR SCREEN
Auxiliary Start Contact (LED)
A back-up LED that indicates when the safety contact
in the starter is closed.
Length of Last Run
Displays the time of the last chiller run in
Day:Hr:Min:Sec format.
PROGRAMMABLE
Rated FLA
Access Level Required: SERVICE
The rated FLA of the compressor motor used to de-
termine the percentage of full load amps displayed.
Service Technicians refer to the Service Instructions
(Form 160.72-M1).
Rated FLKW
Access Level Required: SERVICE
The rated Full Load Kilowatts used to determine the
percentage of full load kilowatts displayed. This calcu-
lation will only be present if the Kilowatts sensor has
been enabled. Service Technicians refer to the Service
Instructions (Form 160.72-M1).
Local Demand Limit
Access Level Required: OPERATOR
Allows the operator to change the Demand Setpoint
from 0 % to 100 %. This will be the Current Limit
Setpoint or the Power Limit Setpoint depending on the
configuration established at commissioning. Service
Technicians refer to the Service Instructions (Form
160.72-M1).
NAVIGATION
Home
Access Level Required: VIEW
Returns user to Home Screen.
Gearbox
Access Level Required: VIEW
Moves to the gearbox screen that shows temperatures
and pressures for the gearbox oil lubrication system
and allows manual control of the auxiliary oil pump,
if equipped.
Anti-Recycle Setpoints
Access Level Required: VIEW
Moves to the anti-recycle setpoints screen that shows
timers and counters for Anti-Recycle operation.