EasyManua.ls Logo

Johnson Controls YORK Tempo YLAA0101HE - Bas;Ems Temperature Reset Usinga Voltage or Current Signal

Johnson Controls YORK Tempo YLAA0101HE
192 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
164
FORM 150.72-NM1 (1020)
Unit Operation
BAS/EMS TEMPERATURE RESET USING
A VOLTAGE OR CURRENT SIGNAL
The Remote Reset Option allows the Control Center
of the unit to reset the chilled liquid setpoint using a
0 - 10VDC input, or a 4-20mA input connected to
XTBC1 terminals A- and A+. Whenever a reset is called
for, the change may be noted by pressing the COOLING
SETPOINTS key twice. The new value will be displayed
as “REM SETP = XXX °F.”
If a 0 - 10VDC signal is supplied, it is applied to
terminals A+ and A-, and jumper JP1 on the I/O board
must be inserted between pins 2 and 3. To calculate
the reset chilled liquid setpoint for values between 0VDC
and 10VDC use the following formula:
Setpoint = Local Chilled Liquid Setpoint + °Reset
°Reset = (DC voltage signal) x (*Max Reset Value)
10
Example:
Local Chilled Liquid Setpoint = 45 °F (7.22 °C)
*Max Reset Value = 20 °F (11.11 °C)
Input Signal = 6VDC
(English)
°Reset = 6VDC x 20 °F = 12 °F Reset
10
New Setpoint = 45 °F + 12 °F = 57 °F
(Metric)
°Reset = 6VDC x 11. 11 °C = 6.67 °C Reset
10
New Setpoint = 7.22 °C + 6.67 °C = 13.89 °C
* Max Reset Value is the “Max EMS-PWM Remote Temp. Reset” setpoint
value described in the program ming section under Cooling Setpoints.
Programmable values are from 2 °F to 40 °F (1.11 °C to 11.11
°C).
If a 4-20mA signal is supplied, it is applied to terminals
A+ and A- and jumper JP1 on the I/O board must be
installed between pin 1 and 2. To calculate the chilled
liquid setpoint for values between 4mA and 20 mA use
the following formula:
Setpoint = Local Chilled Liquid Setpoint + °Reset
°Reset = (mA signal - 4) x (*Max Reset Value)
16
Example:
Local Chilled Liquid Setpoint = 45° (7.22 °C)
*Max Reset Value = 10 °F (5.56 °C)
Input Signal = 12 mA
(English)
°Reset = 8mA x 10 °F = 5 °F Reset
16
Setpoint = 45 °F + 5 °F = 50 °F
(Metric)
°Reset = 8mA x 5.56 °C = 2.78 °C Reset
16
Setpoint = 7.22 °C + 2.78 °C = 10.0 °C
A 24024 Volt Ratio Transformer (T3)
is used to derive nominal 12 volt output
from the 120 volt supply.

Table of Contents

Related product manuals