EasyManua.ls Logo

Johnson Controls YORK Tempo YLAA0101HE - Heat Exchanger Flow, Gpm; Ethylene & Propylene Glycol Correction Factors; Table 3 - Ethylene and Propylene Glycol Correction Factors

Johnson Controls YORK Tempo YLAA0101HE
192 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
48
FORM 150.72-NM1 (1020)
Technical Data
Note: Water Pressure Drop Curves may extend past the minimum and maximum water ow ranges.
HEAT EXCHANGER FLOW, GPM
EVAPORATOR YLAA MODELS
A 70SE
B 80SE
C 91HE,100SE, 101HE, 115SE, 125HE
D 120SE, 141HE, 155SE
E 90SE
F 135SE, 150SE, 156HE, 170HE
G 175HE
YLAA Evaporator Pressure Drop (IP Units)
1.0
10.0
100.0
10 100 1000
Water Flow Rate (GPM)
Pressure Drop (ft H2O)
A
B
C
D
TABLE 3 ETHYLENE AND PROPYLENE GLYCOL CORRECTION FACTORS
ETHYLENE GLYCOL
%
WEIGHT
TONS
kW
COMPR
GPM°F/
TON
PRESS
DROP
FREEZE
PT
10 0.985 0.997 24.1 1.034 26
20 0.981 0.996 24.9 1.062 16
30 0.974 0.995 26.1 1.096 5
40 0.966 0.991 27.5 1.134 -10
50 0.957 0.989 29.1 1.172 -32
PROPYLENE GLYCOL
%
WEIGHT
TONS
kW
COMPR
GPM°F/
TON
PRESS
DROP
FREEZE
PT
10 0.983 0.996 24.2 1.048 27
20 0.974 0.995 24.4 1.086 19
30 0.961 0.990 25.1 1.134 8
40 0.946 0.98 26.0 1.186 -5
50 0.928 0.984 27.2 1.247 -25