FORM 150.72-NM1 (1020)
21
JOHNSON CONTROLS
2
Unit On/O
The microprocessor control center is capable of
displaying the following:
Return and leaving liquid temperature
Low leaving liquid temperature cutout setting
Low ambient temperature cutout setting
Outdoor air temperature
English or Metric data
Suction pressure cutout setting
Each system suction pressure
Discharge pressure (optional)
Liquid Temperature Reset via a Johnson Controls
ISN DDC or Building Automation System (by
others) via a 4 to 20 milliamp or 0 to10 VDC
input.
Anti-recycle timer status for each system
Anti-coincident system start timer condition
Compressor run status
No cooling load condition
Day, date and time
Daily start/stop times
Holiday status
Automatic or manual system lead/lag control
Lead system denition
Compressor starts and operating hours
(each compressor)
Status of hot gas valves, evaporator heater
and fan operation
Run permissive status
Number of compressors running
Liquid solenoid valve status
Load and unload timer status
Water pump status
Provisions are included for: pumpdown at shutdown;
optional remote chilled water temperature reset and two
steps of demand load limiting from an external building
automation system. Unit alarm contacts are standard.
* Intensity of Protection European Standard
** International Electrotechnical Commission
The operating program is stored in non-volatile memory
battery backed RAM to eliminate chiller failure due to
AC powered failure/battery discharge. Programmed
setpoints are retained in lithium battery-backed RTC
memory for 5 years minimum.
COMMUNICATIONS
Native communication capability for BACnet
(MS/TP) and Modbus
Optional communication available for N2 and
LON via eLink option
HIGH AMBIENT KIT
Allows units to operate when the ambient temperature
is above 115°F (46°C). Includes sun shield panels and
discharge pressure transducers.
BUILDING AUTOMATION SYSTEM
INTERFACE
The Microprocessor Board can accept a 4 to 20 milliamp,
0 to10VDC input to reset the leaving chiller liquid
temperature from a Building Automation System.
The standard unit capabilities include remote
start-stop, remote water temperature reset via a
PWM 4 to 20 milliamp or 0 to 10VDC input sig-
nal or up to two stages of demand (load) limiting
depending on model.
The standard control panel can be directly con-
nected to a Johnson Controls Building Automated
System.
POWER PANEL
Each panel contains:
Compressor power terminals
Compressor motor starting contactors per
l.E.C.**
Control power terminals to accept incoming for
115-1-60 control power
Fan contactors and overload current protection
The power wiring is routed through liquid-tight conduit
to the compressors and fans.