TABLE 18 – BACnet MS/TP points (CONT.)
Point ID Point Description
Variable
Type
Read ( R )
Write ( W )
Value
Range
(Analog
Only)
Unit
(Analog
Only)
Instance
Number
Comments
TUESDAYSCHED3
Turns Tuesday On / Off for
Schedule 3:
1 = On – Active
0 = Off – Inactive
BBV R/W - - 897
TUESDAYSCHED4
Turns Tuesday On / Off for
Schedule 4:
1 = On – Active
0 = Off – Inactive
BBV R/W - - 908
TUESDAYSCHED5
Turns Tuesday On / Off for
Schedule 5:
1 = On – Active
0 = Off – Inactive
BBV R/W - - 919
TUESDAYSCHED6
Turns Tuesday On / Off for
Schedule 6:
1 = On – Active
0 = Off – Inactive
BBV R/W - - 930
TUESDAYSCHED7
Turns Tuesday On / Off for
Schedule 7:
1 = On – Active
0 = Off – Inactive
BBV R/W - - 941
TUESDAYSCHED8
Turns Tuesday On / Off for
Schedule 8:
1 = On – Active
0 = Off – Inactive
BBV R/W - - 952
TUESDAYSCHED9
Turns Tuesday On / Off for
Schedule 9:
1 = On – Active
0 = Off – Inactive
BBV R/W - - 964
Unit Enable
Network Unit Start:
1 = Enable
0 = Disable
BBV R/W - - 15001
Unsafe
External Safety Input Alarm:
1 = Fault
0 = No Fault
BBV R - - 15103
VAV Fan En
VAV Fan Enable:
1 = VAV
0 = CV
BBV R/W - - 15010
VFD Sp % by BAS
Communicated Supply Fan
VFD Speed
BAV R 0 -100 % 16024
VFD Sp by BAS En
Enables the Use of a Supply
Fan VFD Communicated Input:
1 = Enabled
0 = Disabled
BBV R/W - - 15013
VFDMod Supply Fan VFD Speed BAV R 0 -100 % 16112
Only with VAV or
FlexSys
User Interface Control Center