COMMISSIONING DATA SHEET (1/2) (STEAM SINGLE-EFFECT ABSORPTION CHILLER)
User:
Model: MFG.No.: User's machine code:
Insulation Resistance Electric Power Supply
Standard: 5 MΩ or more (with 500V megger) R-Gnd S-Gnd T-Gnd
Specication: AC
V / Hz
Circuit breaker MΩ Standard: Within +/- 10% of spec.
R-S V
U-Gnd V-Gnd W-Gnd R-T V
Solution circulation pump MΩ S-T V
Solution spray pump MΩ R-Gnd V
Refrigerant pump (RP) MΩ S-Gnd V
Purge pump (VP) MΩ T-Gnd V
Thermal Relay Setting Refrigerant Purity Temperature Setting
Solution circulation pump A Standard: 1.040 (kg/L) or less Cooling
Solution spray pump A Specic gravity Set. base temp. °F
Refrigerant pump A Turbidity Auto. stop temp. °F
Purge pump A Auto. restart diff. °F
Pump Discharge Pressure Purge Amount
Solution circulation pump PSIG Standard: 4cc/min or less
Solution spray pump PSIG Purge tank cc
Refrigerant pump PSIG Absorber cc