JOHNSON CONTROLS
120
FORM 160.54-O1
PRINTER SCREEN
OVERVIEW
This screen allows denition of the necessary commu-
nications parameters for the printer. Refer to PRINTER
section of this book for details of the Printer connections
and setup.
DISPLAY ONLY
Time Remaining Until Next Print
Displays the time until the next print log will occur, if
the function is enabled.
PROGRAMMABLE
Log Start Time
Access Level Required: OPERATOR
Set the time at which scheduled print logs will begin.
Output Interval
Access Level Required: OPERATOR
Dene the interval at which log printing will occur.
Automatic Printer Logging (Enabled / Disabled)
Access Level Required: OPERATOR
Enable the printer to begin printing status reports be-
ginning at the programmed start time and recurring at
the interval dened above.
Printer Type
Access Level Required: SERVICE
Dene the printer type connected to the chiller sys-
tem.
ACC Auto Map Print (Enabled / Disabled)
Access Level Required: SERVICE
Only available if the chiller system utilizes a Variable
Speed Drive motor controller. The chiller monitors
the ACC communications and when a surge point is
mapped, a short report of system parameters is printed.
When this function is active, all other printing capability
is disabled.
ACC Map Report
Access Level Required: SERVICE
Only available if the chiller system utilizes a Variable
Speed Drive motor controller. The chiller requests the
entire surge map from the ACC. As the map is received,
the parameters for each point are printed.
00319VIP
FIG. 31
OptiView Control Center