FORM 160.77-O2
ISSUE DATE: 11/15/2011
JOHNSON CONTROLS
112
SECTION 5 - DISPLAY MESSAGES
Evaporator Refrigerant Temp Out of Range
The Evaporator Refrigerant Temperature RTD is indi-
cating a resistance that is less than 60 Ohm, or greater
than 160 Ohm. This is outside the normal operating
range of the temperature RTD. This is generally indi-
cates a defective sensor, shorted or loose wire.
Evaporator Refrigerant Temp Temp Low
This message is generated when there is a warning of
an impending trip at 35°F.
Evaporator Refrigerant Temp Very Low
This message is generated when there is a warning of
an impending trip at 34°F.
Primary Discharge Temp Out of Range
The Primary Discharge Temperature RTD is indicating
a resistance that is less than 60 Ohm, or greater than
160 Ohm. This is outside the normal operating range
of the temperature RTD. This is generally indicates a
defective sensor, shorted or loose wire.
Primary Discharge Temp Low
This message is generated when there is a warning of
low discharge superheat.
Primary Discharge Temp Very Low
This message is generated when there is a danger of a
defective sensor.
Primary Discharge Temp High
This message is generated when there is a warning of
an impending trip greater than 210°F.
Primary Discharge Temp Very High
This message is generated when there is a danger con-
dition above 220°F.
Secondary Discharge Temp Out of Range
The Secondary Discharge Temperature RTD is indicat-
ing a resistance that is less than 60 Ohm, or greater
than 160 Ohm. This is outside the normal operating
range of the temperature RTD. This is generally indi-
cates a defective sensor, shorted or loose wire.
Secondary Discharge Temp Low
This message is generated when there is a warning of
low discharge superheat.
Secondary Discharge Temp Very Low
This message is generated when there is a danger of a
defective sensor.
Secondary Discharge Temp High
This message is generated when there is an impending
trip of greater than 210°F.
Secondary Discharge Temp Very High
This message is generated when there is a danger con-
dition above 220°F.
Subcooler Dropleg Temp Out of Range
The Subcooler Dropleg Temperature RTD is indicating
a resistance that is less than 60 Ohm, or greater than
160 Ohm. This is outside the normal operating range
of the temperature RTD. This is generally indicates a
defective sensor, shorted or loose wire.
Oil Sump Temp Out of Range
The Oil Sump Temperature RTD is indicating a re-
sistance that is less than 60 Ohm, or greater than 160
Ohm. This is outside the normal operating range of the
temperature RTD. This is generally indicates a defec-
tive sensor, shorted or loose wire.
Oil Sump Temp Low
This message is generated when there is a warning of
an impending trip less than 70°F, inicating that there is
too much refrigerant dissolved in the oil.
Oil Sump Temp Very Low
This message is generated when there is a low tem-
perature of less than 55°F.
Oil Sump Temp High
This message is generated when there is a warning of
an impending trip greater than 180°F.
Oil Sump Temp Very High
This message is generated when there is a trip caused
by a temperature greater than 185°F.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls York YKEP Series and is the answer not in the manual?

Johnson Controls York YKEP Series Specifications

General IconGeneral
BrandJohnson Controls
ModelYork YKEP Series
CategoryChiller
LanguageEnglish

Related product manuals