6.1 Rooms
Parameter Description Value
AVRNOREARMES Number of resets per thermostat OFF in one day 3
BACPCPMP_OFF Opening for the water pump 5%
BACPCPMP_ON Opening to start the water pump 20%
BACTIH2O_MIN Time lapse for water minimum temperature 5 min.
BACTIRTR Time to reattempt the condition check 20 min.
BACTPDFR_OFF Deactivation temperature of the antifreeze protection 6 °C
BACTPDFR_ON Activation temperature of the antifreeze protection 3 °C
BACTPH2O_MIN Minimum water temperature 30 °C
BACTPIMP_MAX Maximum supply temperature for hot water coil 50 °C
CMPNOTP_ASP_LO Instances that the compressor must be stopped due to error 3
CMPTIASP_LO Suction probe timing 10 min.
CMPTIASP_LO_NO Time during which the instances are counted 60 min.
CMPTION Compressor delay 4 min.
CMPTPASP_LO_1 Cold suction temperature in order to stop the compressor -25 °C
CMPTPASP_LO_3 Repeated cold start-up suction temperature -4 °C
CMPTPEXT_OFF Outdoor temperature at which the compressor is stopped -10 °C
CMPTPEXT_ON Outdoor temperature at which the compressor is started again -8 °C
CO2PCECO_UP Opening slope per air quality 5% / min.
CO2TPMAX Maximum supply temperature 30 °C
CO2TPMIN Minimum supply temperature 15 °C
DFRNOMAX Maximum number of successive defrosts 3
DFRTICONF Defrost confirmation time 3 min.
DFRTICONF2 Defrost confirmation time in outdoor cold 5 min
DFRTIDEF Table of default times between defrosts 30 min.
DFRTIFIN_HI Time for defrost to complete 2 sec.
DFRTIFIN_ME Time for defrost to complete 30 sec.
DFRTIFIN_LO Time for defrost to complete 2 min.
DFRTIMAX Defrost maximum time 10 min.
DFRTISECADO Coil drying time 1 min.
DFRTPEXT Outdoor temperature to apply DFRCONF2 -5 °C
DFRTIVEX Time before completion of the defrost to activate the outdoor fan 10 sec.
DFRTPFIN_HI Defrost end temperature 13 °C
DFRTPFIN_ME Defrost end temperature 5 °C
DFRTPFIN_LO Defrost end temperature 2 °C
DFRTPINICIO Defrost start temperature -3 °C
DISTIREC Maximum temperature recovery time 10 min.
DISTIREC_DFR Temperature recovery time after a defrost 5 min.
DISTPABIERTA Discharge time to be considered for open probe -20 °C
DISTPAVR Discharge temperature fault 130 °C
DISTPCORTO Discharge time to be considered for short circuit 150 °C
DISTPREC_HEAT Recovery time in winter (heat) 35 °C
DISTPREC_COOL Recovery time in summer (cold) 50 °C
ECOPCAPE_DEF Default minimum opening value of the damper 10%
ECOPCDELTA Incremental minimum of the economiser 1,25%
ECOPCENT_OK Enthalpy percent for favourable conditions 5%
ECOTPEXT_MAXLOW Below this temperature the economiser operates 20 °C
ECOTPEXT_MAXHIGH Above this temperature the economiser does not operate 22 °C
ECOTPHIST Hysteresis for ECOTPIMP_MIN 0,5
Operating parameters 6