Stop Bits: 1
Printer type
Access level required: Operator
Using the Printer screen, set the printer type to Weigh-Tronix.
Automatic data logging
Access level required: Operator
If automatic data logging is required, a status report can be automatically printed at a specified
interval beginning at a specified time, using the Printer screen. The interval is programmable over
the range of 1 min to 1,440 min in 1 min increments. The first print occurs at the programmed start
time and occurs at the programmed output interval thereafter. The time remaining until the next
print is displayed on the Printer screen.
Automatic Printer Logging: Enables and disables automatic data logging.
Log Start Time: Enter the time the first print is required.
Output Interval: Enter the preferred interval between prints.
Automatic status reporting
If you require automatic status prints, use the printer screen to set a specified printing interval that
starts at a specified time.
The interval is programmable for a range of 1 min to 1,440 min in 1 min increments. The first print
occurs at the programmed start time and then occur at the programmed output interval. The time
remaining until the next print is displayed on the printer screen.
Automatic printer logging: Enables and disables automatic reporting
Log start time: Enter the time the first print is required
Output interval: Enter the required interval between prints
Note: This is not the same process as continuous datalogging. See .
Downloading system prints to a laptop
Download system reports to a .txt file to capture system operating conditions. Use the following
instructions to establish communication between the OptiView Control Panel and a laptop
computer using HyperTerminal software. Although, any terminal emulation program such as Tera
Term or PuTTY can be used.
Note: The following procedure uses HyperTerminal with a Windows laptop.
1. Connect the laptop computer to the OptiView as shown in the following table.
Table 153: Laptop connections
Laptop (RS-232 Serial Port) OptiView (Com 1)
PIN Description Connector Terminal
2 RX to J2 4 (TXD1)
4 DTR to J2 2 (DSR1)
5 GND to J2 8 GND
Note: The majority of newer laptops do not have a RS-232 port, so a RS-232 to USB
adaptor is required. The adaptor may require you to download a driver. Follow the
instructions for the device you are using.
2. Navigate to the Setpoints > Setup > Printer screen and select Printer Type > PC.