EasyManua.ls Logo

Johnson Controls YORK YVAM - Serial Data Logging

Johnson Controls YORK YVAM
192 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7. On the screen that you need to capture, press the Print button. The HyperTerminal software
displays the printed information, and the information is recorded as a .txt file.
8. When you have recorded the required reports, click Transfer from the toolbar. From the
transfer list, click Capture Text and then click Stop. This stops the transfer and allows access
to the capture file.
9. Do not change the format of the file, the .txt format is preferred for data review.
Serial data logging
When serial data logging is enabled, data values are serially transmitted to the RS-232 port at an
interval defined by the data logging interval. The data is comma separated with a carriage return
and line feed transmitted at the end of each transmission interval from the same snapshot in time.
Figure 67: Communications block diagram
A serial cable that connects the OptiView control panel with the serial port is available from the
YORK parts center (P/N 375-90490-231).
Figure 68: OptiView panel to PC serial cable print connections
YVAM with OptiView Control Center172

Table of Contents

Other manuals for Johnson Controls YORK YVAM