English is the default language. If a language other than English is displayed, an English-speaking
person must navigate to the User screen using the preceding Navigation chart and select English.
Analog input ranges
The following table indicates the valid display range for each of the analog input values. In the
event that the input sensor is reading a value outside of these ranges, the < or > symbols are
displayed beside the minimum or maximum value, respectively.
Table 17: Analog input ranges
English range Metric rangeAnalog input
Low High Unit Low High Unit
Leaving chilled liquid temperature 0.0 133.9 °F -17.7 56.6 °C
Entering chilled liquid temperature 0.0 133.9 °F -17.7 56.6 °C
Evaporator refrigerant temperature 0.0 133.9 °F -17.7 56.6 °C
Discharge temperature 19.8 226.3 °F -6.7 107.9 °C
Discharge pressure 0.0 300.0 psig 0 2068.4 kPag
Suction pressure 0.0 125.0 psig 0 861.8 kPag
Condenser pressure 0.0 300.0 psig 0 2068.4 kPag
Evaporator pressure 0.0 125.0 psig 0 861.8 kPag
Condenser liquid temperature -38.0 187.5 °F -38.8 86.3 °C
Motor housing temperature 10.4 270.0 °F -12.0 132.2 °C
Outdoor ambient air temperature -38.0 213.6 °F -38.8 100.8 °C
Control panel temperature -37.8 198.5 °F -38.7 92.5 °C
Power panel temperature -37.8 198.5 °F -38.7 92.5 °C
Ambient dew point temperature -20.0 120.0 °F -28.8 48.8 °C
VSD coolant temperature -19.7 181.9 °F -28.7 83.2 °C
Note:
(1)
The saturation temperatures are calculated values. They display XXX if the pressure used for
the calculation is out of range.
YVAM with OptiView Control Center44