Compressor screen
Figure 20: Compressor screen
The compressor screen displays a cutaway view of the chiller compressor, revealing the impeller,
and shows all conditions associated with the compressor. Animation of the compressor impeller
indicates whether the chiller is presently in a Run condition. This screen also serves as a gateway to
subscreens for navigating to capacity control and displaying MBC, surge, and VGD and power panel
detail.
Table 30: Display only fields
Field name Description
Discharge Pressure The compressor discharge pressure
Discharge Temperature The temperature of the refrigerant in its gaseous state at discharge of the compressor as it
travels to the condenser
Discharge Superheat The discharge superheat, calculated as Discharge Temperature – Condenser
Saturation temperature
Input % Full Load Amps The chiller current as a percentage of the job input FLA value
Motor % Full Load Amps The current to the motor as a percentage of the motor maximum current
Suction Pressure The compressor suction pressure
VSD Output Frequency The VSD frequency
Table 31: Display only fields: LED
LED name Description
Motor Run ON when the digital output run command to the VSD is on