Schedule screen
Figure 34: Schedule screen
The schedule screen displays the chiller schedule. There are no other display options.
The schedule screen contains more programmable values than the normal display screen.
Programmable values are not linked to a specific button. Use Select to enable the cursor arrows to
highlight the day and the start or stop time you want to modify. Press the Enter (✓) to program the
start and stop times for that day.
You can define a standard set of start and stop times for use every week. You can then specify
exceptions for any day of the week up to six weeks in advance. At the end of each week, the
schedule for the next week is created by combining the standard week definition and the next
defined exception week. The schedule is then updated as each of the exception weeks shifts down,
leaving a new, blank exception week in the sixth week slot.
Table 72: Programmable fields
Button Access Description
Standard Week Start/Stop
Times
Operator
For each day of the week, specify a time for the chiller to start and a time for
the chiller to stop. The times specified are used as the default for every week
of chiller operation.
Exception Start/Stop Times Operator
For each day of the week, specify a time for the chiller to start and stop.
These start and stop combinations may be scheduled up to five weeks in
advance and also for the present week.
Schedule, Enabled or Disabled Operator Enable or disable the monitoring function that enforces the scheduled
starting and stopping of the chiller.
83YVAM with OptiView Control Center