6-11
Connection to gyro (if docking-log option is used)
Term# Function Note
3A NMEA in 3 Connect to NMEA "A" output terminal from
gy
ro
3B NMEA in 3 Connect to NMEA "B" output terminal from
gy
ro
Instead of a serial NMEA interface an analogue signal can be used to obtain rate of turn
information from the gyro.
Term# Function Note
17 Si
g
n. Analo
g
ue in Connect to analo
g
ue output si
g
nal from
gy
ro
17 0VDC Analo
g
ue in Connect to si
g
nal
g
round from
gy
ro
Note! The gyro output impedance may not exceed 150: when using the analogue input.
NWW-82 Speed Log Master Display and redundancy displays
Term# Function Note
37A NMEA out 2 Connect to NWW-82 NMEA "A" input
37B NMEA out 2 Connect to NWW-82 NMEA "B" input
6A NMEA in 6 Connect to NWW-82 NMEA "A" output
6B NMEA in 6 Connect to NWW-82 NMEA "B" output
50+ +12 to 28 VDC Connect to DC power input of displa
y
. Fuse F301
50- 0 VDC Connect to DC power input of displa
y
The speed logs and the Sig. Distributor menu system can be remotely accessed for calibration
and setup of parameters from an NWW-82 Main Display(Master Display).
The NMEA out 2 and NMEA in 6 shall be connected to the NMEA in and out connections of
the SD4 via a twisted pair cable. It is recommended to use a shielded cable with four twisted
pairs to connect the SD4 to the Sig. Distributor, two pairs for NMEA, one pair for power and
one pair as spare. NMEA out 2 will be directly connected, via redundancy relays, to NMEA in
5 (the redundancy output of speed log1) in case of loss of power or a failure in the Sig.
Distributor.
2
nd
Display Log remote control
Term# Function Note
44A NMEA out 9 Connect to NWW-82 NMEA "A" input
44B NMEA out 9 Connect to NWW-82 NMEA "B" input
7A NMEA in 7 Connect to NWW-82 NMEA "A" output
7B NMEA in 7 Connect to NWW-82 NMEA "B" output
51+ +12 to 28 VDC Connect to DC power input of displa
y
. Fuse F301
51 0 VDC Connect to DC power input of displa
y
A 2
nd
Display remote control can be connected to the system. It will have the same remote
control functionality as the Speed log master display.