Options Operation
10-4
10.3 Battery charger (NBB-724)
CAUTION
The batteries, except for sealed lead-acid batteries that require no
equalization, should be carried out the equalizing charge at least every six
months
3 5
4 6
7 8
9
10
1. AC breaker ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ When turned on, enables to use the AC mains input.
2. BATT breaker ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ When turned on, connects the internal circuit to the battery, and
after that turning on the AC breaker enables charging of the
battery. Note that if detected over discharge of the battery
(approx. 19.5V), this breaker trips automatically.
3. BATT LOW alarm lamp ꞏꞏꞏ This lamp turns on and the buzzer sounds to indicate low voltage
of the battery (approx. 21.5V).
4. CHG alarm lamp ꞏꞏꞏꞏꞏꞏꞏꞏꞏ This lamp turns on (or blinks*) and the buzzer sounds to indicate
any one of the following alarms.
・ The BATT breaker is OFF while the AC breaker is ON.
・ Over voltage (equalizing charge voltage + 1.0V)
・ High temperature of the charging circuit (+75℃ )
When AC breaker is OFF and BATT breaker is ON, this
CHG lamp turns on. (This is not a malfunction
.)
5. FLOAT charge lamp ꞏꞏꞏꞏꞏ This lamp turns on during the floating charge operation.
6. EQUAL charge lamp ꞏꞏꞏꞏꞏ This lamp turns on during the equalizing charge operation.
7.
CHARGE mode switch ꞏꞏꞏ
Changes the charge mode between floating and equalizing charge.
8. Dimmer control ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ Adjust the dimmer level.
9. Current meter ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ Indicates the charge current (+) or discharge current (-).
10. Voltage meter ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ Indicates the output voltage of the battery.
1 2
Note