10 Configuration
158
10.10 Digital sensors
10.10.1 General information
Open General Settings Digital Sensors:
Device Menu > Configuration > Digital Sensors > Digital Sensors 1 to 6> Gen-
eral
NOTE
For operation of digital sensors, you need the extra code "JUMO digiLine pro-
tocol activated“ (see Chapter 4.2 "Order Details", page 22)
NOTE
Only one serial interface of the device can be configured for operation of digital
sensors. If your device has 2 serial interfaces (base unit and possibly an op-
tional board), select 1 interface for connection of digital sensors and configure
it appropriately.
NOTE
Correct functioning of digital sensors depends on correctly setting the interface
to which the digital sensors are connected and are to be operated. Make sure
the selected serial interface is configured correctly.
Configuration point Selection/
setting option
Explanation
Parameter No sensor
pH
ORP
Temperature
O-DO
Turbidity
Free chlorine pH-dependent
Free chlorine pH-neutral
Total chlorine
Ozone tenside-dependent
Ozone tenside-neutral
Peracetic acid
Hydrogen peroxide
Chlorine dioxide tenside-dependent
Chlorine dioxide tenside-neutral
Bromide
Free chlorine, open
Sensor type selection
Digital sensors and JUMO digi-Line
electronics can only be linked if of
these settings match the type infor-
mation of the sensor to be linked. If
this setting is changed during opera-
tion of a linked sensor, the sensor in-
volved loses its link and must be put
into operation anew.
with temperature input Yes
No
VdN number 0 to 999