10 Configuration
166
10.10.3 Sensor alarms
Digital sensors cyclically transmit a number of alarm and status bits. In the set-
tings for the sensor alarms, it is possible to set which of these signals should be
indicated on the JUMO AQUIS touch P. The settings for the alarm conditions
themselves are made in the configuration of the individual sensor electronics or
stipulated by the specifications for the particular sensor. More detailed informa-
tion on configuration can be found in the operating manual for the particular sen-
sor type.
Open Sensor Alarms Digital Sensors:
Device Menu > Configuration > Digital Sensors > Digital Sensors 1 to 6>
Sensor Alarms
Every alarm transmitted by the digital sensors has the following configuration
parameters:
The range of alarm types that can be transmitted by a digital sensor depends on
the sensor type. The individual alarm lists for the various sensor types are pro-
vided in the following.
Configuration point Selection/
setting option
Explanation
Alarm/Event list off
event
alarm
Assignment of alarm notification to
alarm list or event list
Sensor alarm
delay
0 to 999 s time delay from receipt of the alarm
signal from the sensor and triggering
of the alarm on the device
Alarm text – Text for the alarm/event list
Displayed only and cannot be
changed.