10 Configuration
10.11.3 Digital signal alarms
Open Alarm Configuration For Binary Inputs:
Device Menu > Configuration > Binary Inputs >
Binary Inputs 1 to 9
Open Alarm Configuration For External Binary Inputs:
Device Menu > Configuration > External Binary Inputs >
External Binary Inputs 1 to 8
Open Alarm Configuration For Logic Formula:
Device Menu > Configuration > Logic Formula > Formula 1 to 30
Configuration point Selection/
setting option
Explanation
Digital signal for hold Selection from the
binary selector
Digital signal for activating the hold function
When the hold function is activated, the alarm as-
sumes the state defined in the "Response at
hold" setting.
Response at hold inactive
active
hold
normal
Specification of the alarm state when the hold
function is activated
inactive: alarm suppressed
active: alarm forced
hold: alarm state is maintained regardless of
alarm condition changes
normal: alarm in acc. with alarm condition
Alarm type active
inactive
Arming or disarming an alarm
Alarm/Event list off
event
alarm
Assignment of alarm notification to alarm list or
event list
Alarm text up to 21 text characters Text for the alarm/event list
Alarm active at high
low
Digital input alarm condition
Alarm delay 0 to 9999 s Time delay between occurrence of the alarm
condition and triggering of the alarm