10 Configuration
10.13.2 Controller inputs
Open: Device Menu > Configuration > Controller > Controller 1 to 4 >
input
Configuration point Selection/
setting option
Explanation
Designation up to 20 text characters Designation of the controller input
Actual value Selection from
Analog selector
Selection of the analog signal source for the ac-
tual value
Output level feedback
signal
Selection from
Analog selector
only for modulating controller and continu-
ous controller with integrated position con-
troller
Selection of the analog signal source for the cur-
rent output level (e.g. universal input with resis-
tance transmitter or analog input with standard
signal)
On continuous controllers with an integrated po-
sition controller, output level feedback is neces-
sary.
Parameter block
switching
Selection from
binary selector
Selection of the digital signal source for switching
from parameter set 1 to parameter set 2
Two parameter sets are stored for each control-
ler and can be switched via this
digital signal.
⇨ Chapter 9.2 "Parameter Sets (Controller pa-
rameter)", page 128
Digital signal for man-
ual
Selection from
binary selector
Selection of the digital signal source to switch the
controller to manual mode
In addition to the button on the
respective controller screen, it is also
possible to activate manual mode with a
digital signal (e.g. key switch for a digital input)
binary signal.
Digital signal for hold Selection from
binary selector
Selection of the digital signal source to switch the
controller to hold mode
Manual text up to 20 text characters Text for the alarm/event list upon activation of
manual mode
Alarm text up to 20 text characters Text for the alarm/event list upon occurrence of a
dosing alarm