EasyManua.ls Logo

JUMO AQUIS touch P - Binary Outputs, Optional Boards; Voltage Supply Outputs, Optional Board

JUMO AQUIS touch P
404 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
373
23 Technical data
23.7 Binary outputs, optional boards
23.8 Voltage supply outputs, optional board
Optional card Switching out-
put
Ampacity at re-
sistive load
Contact life
a
a
The maximal ampacity of the contacts must not be exceeded.
Special features
Relay output, dual nor-
mally open contacts
2 normally open
contacts
b
b
Combining a mains voltage circuit with a protective low-voltage circuit on the "dual normally open con-
tact" option is not admissible.
3 A at AC 250 V 150,000
switching cycles
-
Relay output, single
changeover contact
1 changeover
contact
-
Solid state relay triac Switching out-
put with triac
(protected by
varistor)
c
c
A varistor protects the triac against excessive voltages such as those that can occur during switching.
1 A at AC 230 V Wear-free -
PhotoMOS®
e
solid state relay
Switching out-
put with
PhotoMOS®
d
d
PhotoMOS®
is a registered trademark of Panasonic.
200 mA at
DC 45 V and/or
AC 30 V
Wear-free not short-circuit-
proof
max. voltage
DC 45 V
AC 30 V
Logic output 0/12 V High/low signal 20 mA
e
e
Current limiting via the logic output of the device
Wear-free
-
Logic output 0/22 V High/low signal 30 mA
e
Wear-free
-
Description Output voltage Ampacity Connection
DC 24 V voltage supply
for external transmit-
ters
a
DC 24 V +5 / -5% 42 mA Screw termi-
nals
±5 V DC voltage supply
(e.g. for ISFET pH-sen-
sors)
+5 V DC +10 / 0 %
(between terminals 3 and 4)
150 mA
-5 V DC ±15%
(between terminals 5 and 4)
30 mA
a
An optional board for voltage supply outputs accommodates all the outputs
listed in this table. A maximum of 1 such optional board can be integrated into a
device.