Parameters Setting options,
Default setting
Explanations
Slat change-
over time
300ms ... 10 s
Default setting: 1s
(Venetian blind), 0.3s
(awning)
Absolute time for changing-over Venetian
blind slats. Here, the fabric-stretching
time can be set for the operation of awn-
ings.
Inverse opera-
tion
Off, on
Default setting: off
Inverts the activation of the relay outputs.
During inverted operation, the "Up" and
"Down" relay outputs are controlled ex-
actly the other way around. This is re-
quired, for example, for skylight control-
lers or may help if a Venetian blind / shut-
ter / awning is running in the wrong direc-
tion. This parameter inverts only the be-
haviour of the load outputs, but neither
the operation of the JUNG HOME push-
button nor the display of the running dir-
ection in the app.
Ventilation posi-
tion and slat po-
sition**
Ventilation position: 0 …
100%
Slat position: 0 … 100%
Default setting: 100%
The shutter or the Venetian blind stops in
this position when moving down. The
movement is continued to 100% in the
event of another downward movement
command.
In "Venetian blind" operating mode, the
slats are additionally set to the entered
value.
Note: With JUNG HOME, 0% corres-
ponds to "0% closed", the "upper posi-
tion" or a completely retracted Venetian
blind / awning / shutter.
With JUNG HOME, 100% corresponds to
"100% closed", the "lower position" or a
completely extended Venetian blind /
awning / shutter.
Minimum motor
change-over-
time
300ms ... 10 s
Default setting: 1 s
Minimum interruption time when changing
directions. Increasing the minimum
change-over time will cause less wear on
the motors.
Behaviour after
mains voltage
returns**
Upward movement,
downward movement,
stored position, no
change
Default setting: no
change
Behaviour of the Venetian blind, shutter
or awning after the mains voltage returns
after a power failure.
JUNG HOME push-button 1-gang, JUNG HOME push-button 2-gang