Instructions for operation
- Keep cables between loads (5) and surge protection socket outlet (1) as short as possible,
max. 4 m.
- Do not lay protected cables parallel to unprotected cables. There is a danger of surge
voltage coupling.
- When performing insulation measurements on the system, all surge protection products
should always be disconnected, because otherwise the test voltage will be limited by the
protective modules, thus leading to incorrect measurements.
4 Information for electrically skilled persons
4.1 Fitting and electrical connection
DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
Before carrying out work on the device or load, disengage all the
corresponding circuit breakers. Cover up live parts in the working environment.
Connecting and fitting the device
Figure 2: Connection diagram for single socket outlet
2/4
32515853
J0082515853
05.01.2016
SCHUKO socket with surge voltage protection