4.2.2.3 Cross-section of the supply cable
The conductor cross-section of the supply cable is dependent on the input current, the
cable according to manufacturer's data, as well as the VDE regulations.
4.2.3 Connection at DC voltage supply
- -
U
V
W
PEPEPE
T1 T2
++
+U
-U
1 DC voltage
230V class: 275…373 Vdc
400V class: 480…746 Vdc
2 Fuses
Type aR
Pay attention to the permissible voltage range !
3 KEB COMBIVERT G6
Figure 11: Connection at DC voltage supply
4.2.3.1 Terminal strip X1B DC connection
X1B Name Function Cross-section Tightening torque
++, -- DC connection
AWG
without
wire-end
ferrule
mm²
with
wire-end ferrule
0.5…0.6 A
5…6 lb-inch
24...14 0.25…2.5
Stranded wire
PE,
Connection
for protective
earth
Screw M4
for ring cable lug
1.3 Nm
11 lb inch
Figure 12: Terminal strip X1B DC connection
4.2.4 Connection of the motor
4.2.4.1 Selection of the motor cable
The correct cabling as well as the motor cable play an important part in case of low pow-
er in connection with long motor line lengths. Ferrite cores and low-capacitance cables
(phase/phase < 65 pF /
m, phase/screen < 120 pF / m) at the output have the following
effects:
Longer motor line lengths
Less abrasion of the motor gearbox by leakage currents
Better EMC properties
38
CONNECTION OF THE POWER UNIT

Table of Contents

Other manuals for KEB COMBIVERT G6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT G6 and is the answer not in the manual?

KEB COMBIVERT G6 Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT G6
CategoryDC Drives
LanguageEnglish

Related product manuals