P30 Diagnostic options
FAQ V1.01
29
© KEBA
Each displayed color has a specific significance:
Color Value
Blue 0
White 0
Red 1
The following steps are necessary to calculate the error group:
1) First, the significance of the LED segment must be multiplied by the sig-
nificance of the color.
2) All results obtained are subsequently summed up.
3) The sum is now converted to a hexadecimal digit. This hexadecimal digit
indicates the error group.
Example:
LED segment S1 S2 S3 S4
Color Red Red Blue Blue
Significance of the LED segment 8 4 2 1
Significance of the color 1 1 0 0
Result
(LED segment x color)
8 4 0 0
Error group
(Sum of all results)
12 (decimal) =c (hexadecimal)
=> The error code is: 0x[xxx]c
4.1 Blue/Red error displays
This chapter covers the error messages shown in blue/red on the LED bar.
ERROR_SCHUETZ
Error group: 0x[xxx]1
The switch-on test failed. The contactor in the charging station could not be
switched on. The contactor is not functioning or an internal function has pre-
vented the contactor from being switched on.
Error code Cause
0x9001
The current monitoring has not enabled the activation of the contactor.
The function must be ready before the switching on.
0xa001
The charging controller has not enabled the activation of the contactor.
The function must be ready before the switching on.
0xc001
The contactor is not switched on despite successful activation. The cause
of the fault may lie in the contactor control but also in the contactor itself.