22
EN
The control board has several micro-switches to activate a lot of functions in order to nd suitable solutions for the user and to make the
installation more safety.
3 Operating and regulation modes
3.1 Logic Function
1 2 3 4 5 6 7 8 9 10
DIP
1-OFF 2-OFF
AUTOMATIC 1
By each control it reverse. It recluse automatically at the end of the
pause time.
1-ON 2-OFF
COLLECTIVE USE
When opening and in pause time it doesn’t accept any control, it
reclose automatically at the end of the pause time.
1-OFF 2-ON
PARTIALLY
AUTOMATIC
Each control the sequenze is OPEN-STOP-CLOSE-STOP etc. It
doesn’t reclose automatically.
1-ON 2-ON
AUTOMATIC 2
By each control the sequence is OPEN-STOP-CLOSE-STOP etc.
It reclose automatically at the end of the pause time
1
2
1
2
1
2
1
2
3-ON
Man Present “MAN PRESENT “ function activate Par. 3.2
4-OFF
Lamp
DIP4 OFF if in the terminal board no.15 and 16 is connected to a
SIGNAL LIGHT
4-ON
External
Brake
DIP 4 ON If the terminal board no.15 and 16 is connected to a
mechanic brake.
6 se DIP 4 OFF
Pre-lightin It activate the pre-lighting before the gate’s moving
6 se DIP 4 ON
exterior
brake
Put the DIP in ON if the brake has been activated
or in OFF if it is activated when it is not powered.
7-ON
Internal
Brake
To activate the electronic brake put DIP 7 IN on. WARNING!!!
The inside brake is activated for a while after the motor stops
9-ON 10-ON
Radio partial
opening
If you put the DIP 9 and 10 in ON, you can activate the radio partial
opening (10 poles molex connector).
If you use this function, terminal boards OUT2 should be free.
3.2 MAN PRESENT
If you put the DIP3 the OPEN and CLOSE function changes and also the input for photo-beams
The controls OPEN and CLOSE can be “man present“ function. It means that when the control will be
relased the motor stops immediately.
The controls START/PEDESTRIAN have an automatic function, if the control OPEN and CLOSED are in
use, the control unit won’t accept any control START /PEDESTRIAN untile the gate is closed.
During the “man present” function all safeties are checled but not the obstacle detection. The photo-beams
input is always checked (when the gate is open,too). The gate will stop until the contact is closed.
3