Stratos-Micra INSTALLERS HANDBOOK Iss. 16
setting
type
storage interval
time per division
on chart log
0 Detector output 1 second 10 seconds
1 Detector output 5 seconds 50 seconds
2 Detector output 12 seconds 2 minutes
3 Detector output 30 seconds 5 minutes
4 Detector output 1 minute 10 minutes
5 Detector output 2 minutes 20 minutes
6 Detector output 5 minutes 50 minutes
7 Detector output 10 minutes 100 minutes
8 Detector output 20 minutes 200 minutes
9 Detector output 50 minutes 500 minutes
10 flow recording 1 second 10 seconds
11 flow recording 5 seconds 50 seconds
12 flow recording 12 seconds 2 minutes
13 flow recording 30 seconds 5 minutes
14 flow recording 1 minute 10 minutes
15 flow recording 2 minutes 20 minutes
16 flow recording 5 minutes 50 minutes
17 flow recording 10 minutes 100 minutes
18 flow recording 20 minutes 200 minutes
19 flow recording 50 minutes 500 minutes
The chart log recording rates are as follows.
In the above table the grayed section indicates flow rate recording while the white sec-
tion indicates detector and alarm level recording.
At the slowest recording rate, one month of data can be recorded. The factory default
setting is 8.
If documented figures are unavailable for the fire panel reaction time, compliance
with reaction time regulations may only be verified by post-installation testing.
3.33 Access code – Miscellaneous tab
This is the access code required to amend programmable parameters. The default code
is 0102. Once the appropriate code is entered it may be changed here to any four digit
number to limit unauthorised access.
3.34 Chart recording rate Miscellaneous tab
This function controls how frequently the detector and alarm level or flow rates are
stored in the Stratos-Micra 100’s internal chart recorder log. (See section 4.3, ‘Chart
recording’).