Stratos-Micra INSTALLERS HANDBOOK Iss. 16
8. Event Log
The following screen appears:
An event is defined as
a change to any programmed function
a signal received from an external controller such as the remote software, APIC or
SenseNET
a detector output level meeting or exceeding the Pre-Alarm, Aux, Fire 1 or Fire 2
alarm thresholds
a fault condition such as a flow or separator fault
start of day / night operation
demonstration mode start / stop
FastLearn start / stop
Power on or off
The detector stores an internal log of the last 200 events, and this can either be viewed
on a PC screen or downloaded to disk by use of the remote control software.
When the event log is full (200 events are stored) and a new event occurs, the oldest
event in the log is deleted (First-In, First-Out).
To download the event log, connect a PC to the detector serial port and run the
remote software. Either select the menu options “View Event log” or click on the
event log symbol as indicated below.