Stratos-Micra INSTALLERS HANDBOOK Iss. 16
When the test has finished and no problems have been found, the following screen
appears:
If any problems were found during the diagnostic tests, the nature of the fault will be
indicated in the “Status” column.
Scan: Reads in the status of all connected detectors.
Read Button: This brings up a display of the detector output and flow rate which
updates in real time.
Relays: Brings up a screen allowing the function of the volt-free ‘Fire’ and
Fault LEDs to be tested with the aid of a continuity meter or other
tester. The Fire relay contacts are open in normal operation and will
close on test. The Fault relay contacts operate on a ‘Fail-safe’ basis
and are held closed in normal operation. They will therefore open on
test.
Save As: Saves the summary list of scanned detectors and their status as a text
(.txt) file.
Print: Prints the summary list to a connected printer.