EasyManua.ls Logo

Kidde AirSense Stratos Micra 25 - Flow Fault Error Messages

Kidde AirSense Stratos Micra 25
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 41
Stratos-Micra INSTALLERS HANDBOOK Iss. 16
11.6 Flow fault errors
These occur when the airflow rate into the detector is outside the pre-programmed
limits. As the detector ‘learns‘ the flow setup from the initial installation, this
usually means that there has been some change in conditions. A Flow high fault
may indicate that a sampling pipe is damaged, and a Flow low fault may indicate
that the pipe has been blocked, e.g. by nearby building operations.
If the detector input is sampled from one area and the exhaust is in another area
with different pressure (e.g. the detector is in a roof space and sampling from an
enclosed room), this may lead to flow faults. In this case it would be necessary to
lead a pipe from the exhaust to the protected area to ensure normal flow. This will
require the detector to be installed using the piped exhaust docking station (see
section 6.1).
Intermittent flow faults may indicate local short-term fluctuations in air pressure.
To overcome this problem, the flow fault delay is programmable from 30 to 240
seconds.
11.6.1 "Low flow" error messages.
Check that the pipe giving the error is not blocked
Check that the low flow fault threshold is not set too high (see section 3.29)
In the case of intermittent fault indications, try increasing the flow fault delay time
(see section 3.30).
11.6.2 "High flow" error messages
Check that the pipe is pushed home into the inlet and is not broken or cracked
Check that installed pipe-work is fitted with an end-cap.
PipeCAD
®
pipe modeling software prompts the use of appropriate end-caps.
Open bore pipes are not recommended.
Check that the high flow fault threshold is not set too low (see section 3.28)
In the case of intermittent fault indications, try increasing the flow fault delay time
(see section 3.30).
www.acornfiresecurity.com
www.acornfiresecurity.com

Related product manuals