87
Function
code
Name
Descriptions
Unit
Factory
setting
Modif.
Setting
range
resistor)
1:Enable
Ten’s place of LED:
Not stop when instantaneous stop
function selection
0:Disable
1:Enable(Low voltage
compensation)
Hundred’s place of LED:
Overmodulation selection
0:Disable
1:Enable
b2.03
Overvoltage point
at
stall
120.0%~150.0%Udce
0.1%
140.0%
×
1200~150
0
b2.04
Droop control
0Disable0.01~10.00Hz
0.01
0.00Hz
0~1000
b2.05
Auto current
limiting threshold
20.0%~200.0%Ie
0.1%
150.0%
×
200~2000
b2.06
Frequency
decrease
rate when current
limiting
0.00~99.99Hz/s
0.01Hz
/S
10.00
Hz/s
0~9999
b2.07
Auto current
limiting
selection
0:Invalid at constant speed
1:Valid at constant speed
Note:It is valid all the time at
Acc/Dec
1
1
×
0~1
b2.08
Gain of Slip
compensation
0.0~300.0%
0.1
100.0
0~3000
b2.09
Slip compensation
limit
0.0~250.0%
0.1
200.0
0~2500
b2.10
Slip compensation
time constant
0.1~25.0s
0.1s
2.0s
0~250
b2.11
auto energy-saving
function
0Disable
1Enable
1
0
×
0~1
b2.12
Frequency
decrease
rate at voltage
0.00~99.99Hz/s
0.01Hz
/S
10.00
Hz/s
0~9999