SET POINT: temperature control room
lower alarm limit temperature of the room
higher alarm limit temperature of the room
deFrost repetition time in hours
code to enter parameter’s menu = “22"
with Cod=1 and exit the menu back to factory settings
differential operating temperature of SPo
In case of sensor’s malfunction (LF1), the compressor operates as follows:
0 = 40% compressor’s operation (3min ΟΝ, 4min OFF),
1 = 100% compressor’s operation (ΟΝ continuously).
minimum pause time of the compressor
maximum duration of deFrost
Temperature limit of deFrost: above this temperature the automatic deFrost stops and it is not possible to
start the procedure again manually.
Manual deFrost lasts 20 min and does not stop based on “dLE” temperature limit.
type of deFrost: compressor OFF (not programmable)
dripping time, in which the compressor remains OFF after deFrost ends
During deFrost the indication “dFr” is displayed, where: 0 = the room’s temperature is displayed during defrost.
zero adjustment of temperature sensor
time delay for refreshing the temperature indication on screen
switch °C/°F (0=°C, 1=°F) ATTENTION: changes between °C/°F do not apply on SPo
time response of the device to the CAMIN network
Fan’s relay operation (1=ON continuously, 0=ON when the compressor is ON). The fan operates during deFrost.
serial input operating mode, where 0 = operates with the network and the serial key,1 = connects with an
external device for exporting alarms. ATTENTION: if the value in
“Add” parameter is ≠ 0, then the “Ufu” is programmed automatically to 0.
minimum temperature limit of SPo
maximum temperature limit of SPo.
Door input polarity (0=OFF, 1=ON with ΝΟ contact, 2=ΟΝ with NC contact). When the door opens, the fan
turns OFF immediately.
Start delay time alarm, where:
0 = activate immediately,
1 ÷ 120 min = the alarm is activated after the selected minutes.
For sensor and door failure alarms, the above rules do not apply.
address of the device in the CAMIN network
Made in Greece.
ATTENTION according to safety standards, the device must be properly positioned and protected from any contact with electrical parts. All parts that provide protection must
be fastened in such a way that they cannot be removed without the use of tools. ATTENTION: disconnect the power supply of the device before proceeding to any kind of
maintenance. ATTENTION: do not place the device near heat sources, equipment containing strong magnets, in areas affected by direct sunlight or rain. ATTENTION:
prevent electrostatic discharges at the side slots of the device and sharp objects from been inserted. ATTENTION: separate the signal's cables from the power supply's
cables to prevent electromagnetic disorders. Signal cables must never be in the same pipe with the power supply cables. Use the device only as described in this
document, not to use itself as a security device. The device must be disposed of in accordance with local standards for the collection of electrical and electronic
equipment. Read and keep these instructions. The device is under two year's guarantee of good operation. The guarantee is valid only if the manual instructions have
been applied. The control and service of the device must be done by an authorized technician. The guarantee covers only the replacement or the service of the device.
preserves the right to adjust its products without further notice.
392 Mesogeion Avenue 153 41 Τ:+30 210 6533730 F:+30 210 6546331 info@kiour.com www.kiour.com
cabinet sensor malfunction
alarm low temperature in the cabinet
alarm high temperature in the cabinet
open door alarm ( if the door is open more than 2min the alarm is activated and the compressor stops)
The alarms are automatically deactivated when the cause of the alarm disappears.