3.3 Engine oil level is low, but engine does not stop. (Defective oil switch)
Drain out oil completely, disconnect alarm
connection wire, and check the continuity
between alarm outlet terminal and ground.
Replace the oil level alarm
Ignition module fault: replace module.
Continuity
Reset the alarm connection wire, disconnect
ignition module and check the continuity
between the plug orange wire and ground.
No continuity
Repair or replace the wire
harnesses
Continuity
No continuity
3.4 Engine stops running (Throttle is at the correct position)
Check the oil level and oil alarm
Fill in oil and restart the engine
Sufficient oil
Oil alarm
Check whether there is enough fuel in the
fuel tank.
A
dd fuel and restart the engine
No fuel
Sufficient fuel
Check the fuel switch and fuel filter fo
r
blockage
Check the fuel supply line for blockage
Clear or replace the fuel supply
line
Blocked
No blocked
Clean or replace carburetor
Blocked
Check the carburetor nozzles for blockage
No blocked
Blocked
Clear the fuel switch and fuel
filter
Not blocked
Check seal between inlet gasket and
carburetor heat insulation block
Normal
Measure the cylinder compression
1. Check the valve clearance
2. Check the carbon deposit in
combustion chamber
3. Check the piston, piston ring
and cylinder for damage
Abnormal
Tighten nuts and/or replace
gasket.
Abnormal
Normal
Check the trigger clearance
Abnormal
Normal
Perform the throttle control system test
Readjust the trigger clearance
15